3 Conductor
Unshielded VNTC - 3 Conductor w/Ground, UL Type TC-ER, 600 V, 90°C dry and wet rated - RoHS
Bend Radius: 5 x overall diameter installed (up to 2.0") / 6 x overall diameter installed (over 2.0")
8 x overall diameter during installation pull-in.
Notes:
• Dimensions and weights shown are nominal values, subject to standard industry tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct
buried at 30°C ambient temperature and 90°C rated conductors.
• For correction factors for different ambient temperatures and ampacities at different conductor
temperature ratings see NEC Table 310.15(B)(16).
(1) NEC Article 240.4(D) requires that over current protection not exceed 15 amperes for 14 AWG
copper conductors, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors after
any correction factors for ambient temperature and number of conductors have been applied.
Exceptions to this may be covered in NEC Article 240.4(E) through (G).
• Control conductors are color coded E-2
• Power conductors are black with numbers - M4
• Fillers where applicable.
Scroll to add product to your quote.
Cole Number | Size AWG | No. Of Cond. | JKT Wall | Insul Wall | NOM O.D. | Ground AWG | D.C. Volts | AMPS (1) | Weight LBS/MFT | Color | Quantity | Add |
---|---|---|---|---|---|---|---|---|---|---|---|---|
16-3050 | 14 | 3 | 45 | 15/4 | .350 | 14 | 600V | 25 | 90 | |||
16-3091 | 12 | 3 | 45 | 15/4 | .368 | 12 | 600V | 30 | 126 | |||
16-3121 | 10 | 3 | 45 | 20/4 | .450 | 10 | 600V | 40 | 202 | |||
16-0350 | 8 | 3 | 60 | 30/5 | .610 | 10 | 600V | 55 | 302 | |||
16-0352 | 6 | 3 | 60 | 30/5 | .725 | 8 | 600V | 75 | 422 | |||
16-0354 | 4 | 3 | 80 | 40/6 | .857 | 8 | 600V | 95 | 647 | |||
16-0356 | 2 | 3 | 80 | 40/6 | .986 | 6 | 600V | 130 | 963 | |||
16-0358 | 1 | 3 | 80 | 50/7 | 1.108 | 6 | 600V | 150 | 1156 | |||
16-0360 | 1/0 | 3 | 80 | 50/7 | 1.207 | 6 | 600V | 170 | 2159 | |||
16-0362 | 2/0 | 3 | 80 | 50/7 | 1.297 | 6 | 600V | 195 | 1738 | |||
16-0364 | 3/0 | 3 | 80 | 50/7 | 1.410 | 4 | 600V | 225 | 2122 | |||
16-0366 | 4/0 | 3 | 80 | 50/7 | 1.530 | 4 | 600V | 260 | 2576 | |||
16-0368 | 250 | 3 | 110 | 50/7 | 1.739 | 4 | 600V | 290 | 3128 | |||
16-0370 | 350 | 3 | 110 | 60/8 | 1.961 | 3 | 600V | 350 | 4347 | |||
16-0372 | 500 | 3 | 110 | 60/8 | 2.234 | 2 | 600V | 430 | 5819 |