12AWG (1)
XLP/PVC Tray Cable Unshielded Multiconductor Tray Cable 12 AWG
Multiconductor 12 AWG Type XHHW-2
Insulation Thickness: 30 mils /0 .76 mm
Conductor: Bare, annealed copper conforming to ASTM B3 and Class B stranded in accordance with ASTM B8.
Insulation: Flame-retardant cross-linked polyethylene meeting the requirements for XHHW-2 per UL 44 and the requirements of ICEA S-95-658
for XLPE insulation as standard. Rated VW-1
Assembly: Conductors are cabled in concentric layers with interstices filled with suitable fillers, as required. Ground wires, are sized as required by UL 1277
(refer to the applicable product tables for the standard provided). Cable has an insulated green ground wire.
A binder tape of synthetic material assembles the core in a tight circular configuration.
Jacket: UL listed sunlight and moisture resistant, sequentially length marked, black polyvinyl chloride (PVC) material meeting the requirements of UL 1277.
Bend Radius: 5 x overall diameter installed / 8 x overall diameter during installation pull-in.
Notes:
• Dimensions and weights shown are nominal values, subject to standard industry tolerances.
• Cables with different conductor counts and bare or insulated green grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance
with NEC 2008 and NEC 2011 Article 336.10(7).
• Ampacities are in accordance with NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16) for conductors
in raceway or direct buried at 30°C ambient temperature and 90°C rated conductors. Ampacities
for cables having more than three conductors have been derated per NEC 2008
Table 310.15(B)(2)(a) or NEC 2011 Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC 2008 Table 310.11(B) or NEC 2011 Table 310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor
temperature ratings see NEC 2008 Table 310.16 or NEC 2011 Table 310.15(B)(16).
• NEC 2008 and NEC 2011 Article 240.4(D) requires that overcurrent protection not exceed
20 amperes for 12 AWG copper conductors after any correction factors for ambient temperature
and number of conductors have been applied. Exceptions to this may be covered in NEC 2008
and NEC 2011 Article 240.4(E) through (G).
(1) Where 4th conductor is neutral of a balanced 3 phase system.
Scroll to add product to your quote.
Cole Number | Size AWG | No. Of Cond. | JKT Wall | NOM O.D. | D.C. Volts | AMPS (1) | Weight LBS/MFT | Color | Quantity | Add |
---|---|---|---|---|---|---|---|---|---|---|
16-0414 | 12 | 2 | 45 | .420 | 600V | 30 | 94 | |||
16-0415 | 12 | 3 | 45 | .445 | 600V | 30 | 126 | |||
16-0416 | 12 | 4 | 45 | .485 | 600V | 24/30 | 160 | |||
16-0417 | 12 | 5 | 45 | .535 | 600V | 24 | 194 | |||
16-0418 | 12 | 7 | 60 | .610 | 600V | 21 | 273 | |||
16-0419 | 12 | 9 | 60 | .710 | 600V | 21 | 341 | |||
16-0420 | 12 | 10 | 60 | .755 | 600V | 15 | 356 | |||
16-0421 | 12 | 12 | 60 | .795 | 600V | 15 | 416 | |||
16-0422 | 12 | 15 | 60 | .860 | 600V | 15 | 506 | |||
16-0423 | 12 | 19 | 80 | .955 | 600V | 15 | 655 | |||
16-0424 | 12 | 20 | 80 | .995 | 600V | 15 | 691 | |||
16-0425 | 12 | 25 | 80 | 1.115 | 600V | 13.5 | 847 | |||
16-0426 | 12 | 30 | 80 | 1.190 | 600V | 13.5 | 995 | |||
16-0427 | 12 | 37 | 80 | 1.265 | 600V | 12 | 1275 |